 4-Line Filters for Converters and Power Electronics
Power line filters for three-phase systems Rated voltage 440/250 V~, 50/60 Hz Rated current 16 to 1600 A Construction
Four-line filter Metal case Threaded bushes at end faces for
B84144
RF-tight installation Features

Low leakage current Easy to install Degree of protection up to 180 A: IP 201) Space-saving design Design based on EN 133200, UL 1283, CSA 22.2 No.8 1986
Applications

General-purpose application in power electronics UPS Wind farms For machine tools, textile and packaging machines
Terminals
Safe-to-touch terminal blocks for filters up to 180 A Busbars for filters 250 to 1600 A
Marking Marking on component: Manufacturer's logo, ordering code, rated voltage, rated current, date code Minimum marking on packaging: Manufacturer's logo, ordering code
1) In accordance with IEC 60529: 1989; EN 60529: 1991; DIN VDE 0470-1
274 04/02
4-Line Filters for Converters and Power Electronics
Typical circuit diagram
LINE L1 LOAD L1'
B84144
L2
L2'
L3
L3'
N PE
N' PE
SSB1076-F
Technical data Rated voltage V R Rated current I R Test voltage V P 440/250 V~, 50/60 Hz Referred to 40 C ambient temperature 1770 V-, 2 s (line/line) 2700 V-, 2 s (lines/case), for 16 ... 50 A 2550 V-, 2 s (lines/case), for 80 ... 180 A 2121 V-, 2 s (lines/case), for 250 ... 1600 A 1,5 * IR for 3 min per hour or 2,5 * IR fur 30 s per hour at 400 V~, 50 Hz 25/100/21 (- 25 C/+100 C/21 days damp heat test) in accordance with EN 60068-1
Overload capability Leakage current Ileak Climatic category
275 04/02
4-Line Filters for Converters and Power Electronics
Characteristics and ordering codes IR A 16 25 36 50 80 120 150 180 250 500 1000 1600 Terminal cross section mm2 4 10 10 10 25 50 50 95 Busbars I leak mA Rtyp m 10 6 3,5 1,3 0,7 0,5 0,35 0,25 0,095 0,060 0,030 0,020 PV W 8 11 14 10 13 22 24 24 18 45 90 150 Approx. weight kg 2,2 3,7 3,7 4,0 9,5 10 10 13 32 53 140 185
B84144
Ordering code
< 3,5 < 3,5 < 3,5 <6 <6 <6 <6 <6
<6 <6 <6 <6
B84144-A16-R B84144-A25-R B84144-A36-R B84144-A50-R B84144-A80-R B84144-A120-R B84144-A150-R B84144-A180-R B84144-G250-S B84144-G500-S B84144-G1000-S B84144-G1600-S
276 04/02
4-Line Filters for Converters and Power Electronics
Dimensional drawings B84144-A16-R
20,50,5
B84144
81 max.
550,4
361
PE M6 x 25 163 max. 700,2
12,50,4
10,1
600,4 86 max.
4 x M5/6/mm tief deep x M5 6 mm
12,51
N L3 L2 L1
N L3 L2 L1 1000,3
Marking LINE LOAD
5,50,1 141 max.
Anschlussklemmen Terminal blocks 4 mm 22 4 mm
113 max.
SSB1077-N
B84144-A25-R ... B84144-A50-R
310,5
91 max.
650,4
301
461
12,50,4
10,1
PE M6 x 25 216 max. 800,2
1000,4 22,51 126 max. 4 x M6/6/mm tief deep x M6 6 mm
L2 L1
N L3
LINE
LOAD
6,60,2 166 max.
Anschlussklemmen Terminal blocks 10 mm 2 10 mm2
N L3
156 max.
1400,3
Marking
L2 L1
SSB1078-W
277 04/02
301
4-Line Filters for Converters and Power Electronics
B84144-A80-R
48,50,5
B84144
141 max.
181
1100,4
1,20,1
831
150,4
PE M10 x 35 300 max. 1150,2
1100,4 141 max.
4 x M6/6/mm tief deep x M6 6 mm
L1
L1
N
LINE
LOAD
6,60,2 221 max.
N
1550,3
Marking
Terminal blocks 25 mm 2 25 mm2
Anschlussklemmen
SSB1079-5
B84144-A120-R, B84144-A150-R
540,5
181
171 max.
L2
L3
L3
L2
141 max.
1100,4
1,20,1
871
150,4
PE M10 x 35 348 max. 1150,2
1100,4 141 max.
4 x M6/6/mm tief deep x M6 6 mm
N L3 L2 L1
N L3 L2 L1
LINE
LOAD
6,60,2 261 max.
Anschlussklemmen Terminal blocks 50 mm2 50 mm 2
1550,3
Marking
171 max.
SSB1086-M
278 04/02
551
551
4-Line Filters for Converters and Power Electronics
B84144-A180-R
B84144
141 max.
160,5
1051
1200,4
740,5
1,20,1
100,4
PE M10 x 35 404 max. 301 max.
1100,4 141 max. 4 xxM6/6 mmmm deep 4 M6 / 6 tief
L1
L1
Marking LINE LOAD
6,60,2 82,50,2
82,50,2
Terminal blocks 95 mm2 2
Anschlussklemmen 95 mm
171 max.
L2
L2
155 0,3
L3
N
N
L3
SSB1087-V
279 04/02
620,8
4-Line Filters for Converters and Power Electronics
B84144-G250-S
4 x M8 x 7 4 x M8 x 7
B84144
350+3
1900,5 L2 L1
110 171_ 4
L3
4,50,5 1050,5
N
N
4
PE M10 x 30 2001 30 o10,5
PE M10 x 30
o12
L3 L2/ N L1 LINE Marking LOAD
L3
241
L2/ N L1
230+2
2601
24
120
15 _ 3 = 3703 4606 =
SSB0996-A
280 04/02
285
34
N
48
89,5
4-Line Filters for Converters and Power Electronics
B84144-G500-S
4 x M8 x 7 4 x M8 x 7
B84144
500
2100,5 L2
60,5
1500,5
L3
L1
N
N
N
6
PE M10 x 30 2801 30 o11 L3 L2/ N L1 LINE Marking LOAD
PE M10 x 30
26
60 150
o12
L3
30+3
L2/ N L1
2801
250
15 +1 = 5103 5903 =
SSB0997-I
281 04/02
305
56,5 101,5
134,5 198 _ 4
4-Line Filters for Converters and Power Electronics
B84144-G1000-S
4 x M8 x 7 4 x M8 x 7
110,5
B84144
650+4
3600,8 L3
2400,8
L2
L1
78 163 211 290 _ 3
SSB0998-R
N PE M12 x 30 3201 o14 L3 L2/ N LINE L1 Marking LOAD 40 o12
N
8 28
N
38
PE M12 x 30
65 262
L3 L2/ N L1
50+10 400+3 4401 465
40 = 6603 8403 =
20+1
282 04/02
4-Line Filters for Converters and Power Electronics
Mabild B84144-G1600-S
4 x M8 x 7 680+4 4 x M8 x 7 3600,8 L3 L2 L1
B84144
110,5 2400,8
N PE M12 x 30 3401 o14 L3 L2/ N LINE L1 Marking LOAD 40 o12
N
N
8
PE M12 x 30
262
L3 L2/ N L1
40 = 6903 8703 =
50+10 400+3 4401 465
20 +1
SSB0999-Z
283 04/02
38
65
28
78 163 211 290 _ 3
4-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84144-A16-R ... -A36-R
100
SSB1677-Q
B84144
B84144-A50-R
100
SSB1678-Y
e
dB 80
e
dB 80
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
0 10 4
10 5
10 6
10 7
Hz 10 8 f
B84144-A80-R
100
SSB1090-F
B84144-A120 ... -A150-R
100
SSB1091-N
e
dB 80 70 60 50 40 30 20 10 0 10 4 10 5 10 6 10 7 Hz 10 8 f
e
dB 80 70 60 50 40 30 20 10 0 10 4 10 5 10 6 10 7 f Hz 10 8
284 04/02
4-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84144-A180-R
100
SSB1092-W
B84144
B84144-G250-S ... -G1600-S
100
SSB1000-K
e
dB 80 70 60 50 40 30 20 10 0 10 4 10 5 10 6 10 7 f Hz 10 8
e
dB 80
60
40
20
0
10 4
10 5
10 6
10 7
Hz 10 8 f
285 04/02
(
Herausgegeben von EPCOS AG Unternehmenskommunikation, Postfach 80 17 09, 81617 Munchen, DEUTSCHLAND ++49 89 636 09, FAX (0 89) 636-2 26 89
EPCOS AG 2002. Vervielfaltigung, Veroffentlichung, Verbreitung und Verwertung dieser Broschure und ihres Inhalts ohne ausdruckliche Genehmigung der EPCOS AG nicht gestattet.
Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen fur Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird. Diese Broschure ersetzt die vorige Ausgabe. Fragen uber Technik, Preise und Liefermoglichkeiten richten Sie bitte an den Ihnen nachstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland. Bauelemente konnen aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskunfte daruber bitten wir unter Angabe des betreffenden Typs ebenfalls uber die zustandige Vertriebsgesellschaft einzuholen.
EPCOS AG 2002. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless otherwise agreed. This brochure replaces the previous edition. For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or the international Representatives. Due to technical requirements components may contain dangerous substances. For information on the type in question please also contact one of our Sales Offices.
(
Published by EPCOS AG Corporate Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY ++49 89 636 09, FAX (0 89) 636-2 26 89
1


▲Up To Search▲   

 
Price & Availability of B84144-G500-S

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X